Fluke 43B Power Quality Analyzer
|
Item Number: FLUKE-43B/003
Manufacturer: Fluke
Part Number: FLUKE-43B/003
* Whole number only
|
|
Fluke 43B Power Quality Analyzer  Maintain power systems, troubleshoot power problems, diagnose equipment features. The Fluke 43B Power Quality Anayzer performs the measurements you need to maintain power systems, troubleshoot power problems and diag- nose equipment failures. All in a ruggerd handheld package. Features:
- Calculates three-phase power on balanced loads from a single-phase measurement
- Measures power harmonics, and captures voltage sags, transients, and inrush currents
- Monitoring functions help track intermittent problems and power system performance
- Menus use familiar electrical terminology
- Toggle through the most commonly used power quality modes with a single keystroke
- Records two selectable parameters for up to 16 days
- 20 measurement memories to save/recall screens and data with cursor readings
- FlukeView Software can log harmonics and all other readings over time
- FlukeView Software provides a complete harmonics profile up to the 51st harmonic
- Measures resistance, diode voltage drop, continuity, and capacitance
|

- Voltage, current, and power harmonics
- Up to 51st harmonic
- Total harmonic distortion (THD)
- Phase angle of individual harmonics
|
 On-screen graphics show you how to set up 3-phase power measurements
|
|

- One and three phase power on balanced loads
- Watts, power factor, displacement power factor, VA and VAR
- Voltage and current waveforms
|

- Continuously measure volts and current on a cycle-by-cycle basis for up to 16 days
- Use cursors to read time and date of sags and swells
|
|

- Catch voltage transients and waveform distortion
- Catch and save up to 40 transients
- Correlate the cause of transient with time and date stamps
|

- Voltage and current waveforms
- True RMS voltage and current
- Frequency
|
Specifications:
| Input Characteristics |
Ranges
|
Accuracy
|
| Input Impedance |
1MW |
|
| Voltage rating |
600V rms, CAT III |
|
| Volt/Amps/Hertz Display |
| True-rms voltage(ac + dc) |
5.000V, 50.00V, 500.0V, 1250V |
±(1%+10 counts) |
| True-rms current(ac + dc) |
50.00A, 500.0A, 5.000kA, 50.00kA |
±(1%+10 counts) |
| Mains Frequency |
40.0 to 10.0Hz |
±(0.5%+2 counts) |
Power, Watts, Volt-Amps, VA Reactive Volt-Amps, VAR |
250W, 2.50kW, 25.0kW, 250kW, 2.5MW |
±(1%+1 counts) |
Power Factor, PF, Displacement Power Factor, DPF |
0.00 to 0.25, 0.25 to 1.0 |
Not Specified ±0.01 |
| Harmonics Display |
| Voltage |
1st to 51st harmonic |
±(3%+2counts) to ±(15%+5counts) |
| Current |
1st to 51st harmonic |
±(3%+8 counts) to ±(5%+8 counts) |
| Power |
1st to 51st harmonic |
±(5%+2 counts) to ±(30%+5 counts) |
| Line Frequency |
40 Hz to 70 Hz fundamental |
±0.25 Hz |
| Phase |
2nd to 51st harmonic |
±3° to ±15° |
| K-factor |
1.0 to 30.0 |
±10% |
| Sags and Swells Recording |
| Recording Times |
4 min to 16 days (selectable) |
| Installed battery |
Rechargeable Ni-Cd pack |
| Operating Time |
4 hours |
| Temperature |
0°C to 50°C(32°F to 122°F) |
| Size(H x W x D) |
232 x 115 x 50mm(9.1 x 1.5 x 2inches) |
| Weight |
1.1 kg(2.5 lbs) |
| Surge protection |
6kV on input A and B |
| Included Accessories |
| TL24 Test Leads |
| AC85 Large Jaw Alligator Clips |
| Power Quality Video |
| 80i-500s 500A AC Current Clamp |
| TP4 4mm Round Slim-Reach™ Test Probes |
| SW43W FlukeView® Analyzer Software for Windows |
| PM 9080/001 Optically Isolated RS232 Interface Adapter |
| BP120 Rechargeable Ni-Cd Battery Pack (installed) |
| PM 8907 Line Voltage Adapter/Battery Charger |
| Sheilded Bannana-to-BNC Adapter |
| FlukeView® Power Quality Analyzer Users Manual |
| AC20 Industrial Test Clips |
| TP1 Fast-tipped Slim-Reach™ Test Probes |
|
Product Reviews
|
|